UPS5000-E-120K-F120 is a high performance uninterruptible power system which can provide high efficient and reliable power protection to central offices or medium data centers in telecommunication, finance, government, transportation, etc. It features modular design and can output 40-120 kVA power protection with rated capacity of 380/400/415 V AC. Benefiting from hot-swap design of key components that reduces mean time to repair greatly, the system reliability and availability is well improved.
Features : Reliable
- Wide input voltage and frequency range: 138-485Vac, 40-70Hz
- 5kA lighting protection design on input port to reduce lightning-related failure rate
- Redundant design and hot-swappable controllers, which improve the reliability of the whole system
Features :Efficient
- High efficiency of up to 96% at online mode
- Intelligent hibernation technology to improve operation efficiency and reduce the UPS power loss efficiently
Features :Convenient
- Hot swappable power modules, control modules, and bypass modules make module replacement time close to 0, which facilitates capacity expansion and maintenance
- High power density of up to 40kVA/3U, and only 0.5 square meters taken up
- High output power factor of up to 1 and 25% more load driven
- The 7-inch colored LCD in standard configurations
Features :Intelligent
- Intelligent battery management to extend battery service time by 50%
- Built-in SNMP card and HUAWEI Neteco 1000 software, easy to manage remotely
Model | UPS5000-E-120K-F120 | ||
---|---|---|---|
Rated Capacity (kVA / kW) |
40 | 80 | 120 |
The Number of Power Modules | 1 | 2 | 3 |
Dimensions (H×W×D) | 2000 mm × 600 mm × 850 mm | ||
Weight | 227 kg | 260 kg | 293 kg |
Input | |||
Input Wiring | 3Ph+N+PE | ||
Rated Voltage | 380/400/415 V AC | ||
Input Voltage Range | 138-485 V AC; 305-485 V AC for 100% load; 305V-138 V AC for 100%-40% load (derating linearly) | ||
Input Frequency Range | 40-70 Hz | ||
THDi (Total Harmonic Distortion of Input Current) | THDi<3% (for linear load); THDi<5% (for nonlinear load) | ||
Input Power Factor | 0.99 | ||
Bypass Voltage | 380/400/415 V AC | ||
Bypass Input Wiring | 3Ph+N+PE | ||
Bypass Frequency Range | 50/60±6 Hz | ||
Battery Voltage | 360-480 Vdc | ||
Output | |||
Output Wiring | 3Ph+N+PE | ||
Output Voltage | 380/400/415 V AC±1% | ||
Output Frequency | Tracking the bypass input (online mode); 50/60 Hz±0.1% (battery mode) | ||
Waveform | Sine wave; THDv<1% for 100% linear load and THDv<3% for 100% nonlinear load | ||
Output Power Factor | 1 | ||
System Efficiency | 96% | ||
Overload Capacity | Inverter: 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minutes Bypass: 135% overload for long term; >1000% overload for 100 ms |
||
Environment | |||
Operating Temperature | 0-40? | ||
Storage Temperature | -40-+70? | ||
Relative Humidity | 0%-95% (non-condensing) | ||
Operating Altitude | 1000 m; above 1000 m, derating 1% for each additional 100 m | ||
Audible Noise | ?65dB | ||
Others | |||
Certifications | EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; Rohs, Reach, WEEE, etc. | ||
Communication Interfaces | Dry Contacts, RS485, SNMP |
Item | Detail |
---|---|
Communication card | -- Dry contact extended card -- Backfeed protection card |
Powerdistribution | -- Input power distribution cabinet -- Output power distribution cabinet -- Battery switch box -- Battery circuit breaker (BCB) box |
Battery Management kit | -- Battery monitoring unit -- Battery ground fault detector |
Environment | -- Ambient temperature and humidity sensor -- Battery temperature sensor |
Mechanical kit | -- Top outlet kit -- IP21 component -- Antiseismic kit |