Germin-XP is an on-line double conversion UPS (VFI SS 111 in accordance with IEC EN 62040-3 ) with a transformer isolated inverter. Germin-XP has a compact foot print and high quality output to provide the ultimate power protection for 'mission critical'.
Application: Data processing/Telecommunication/Industrial process/Business(Server,ISP,ASP,PoP)/Security/Electro Medical System/Service/Emergency Device(Light,Alarm)
Specification
Model | GM10-XP | GM15-XP | GM20-XP | GM30-XP | GM40-XP | GM60-XP | GM80-XP | GM100-XP | GM120-XP |
Power (KVA/KW) | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | 100KVA/80KW | 120KVA/96KW |
Input | |||||||||
Norminal Voltage | 380-400-415 Vac three-phase | ||||||||
Voltage tolerance | 400V +20%/-25% | ||||||||
Frequency range | 45-65Hz | ||||||||
Solf Start | 0 - 100% in 30' (selectable) | ||||||||
Permitted Frequebcy Tolerlance | ±2% (selectable from ± 1% to ± 5% from the front panel) | ||||||||
Standard feature | Back Feed protection; separable bypass line | ||||||||
Battery | |||||||||
Type | I ead, flooded and VR A AGM / GEI ; NiCd | ||||||||
AC ripple | < 1% | ||||||||
Temperature compensation | -0.5V x oC | ||||||||
Typical charging current | 0.2 x C10 | ||||||||
Output | |||||||||
Rated power (kVA) | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 | 120 |
Active power (kW) | 8 | 12 | 16 | 24 | 32 | 48 | 64 | 80 | 96 |
Number of phase | 3 + N | ||||||||
Norminal Voltage | 380-400-415 Vac three-phase+N | ||||||||
Power Factor | 0.8 | ||||||||
Static stability | ±1% | ||||||||
Dynamic stability | ±5% in 10ms | ||||||||
Voltage distortion | < 1% with linear load/3% with no-linear load | ||||||||
Crest factor (Ipeak/Irms) | 3:01 | ||||||||
Freq. stability on battery mode | 50 or 60Hz (selectable) | ||||||||
Overload | 110% for 60'; 125% for 10'; 150% for 1' | ||||||||
Environment | |||||||||
Weight (kg) without battery | 210* | 220* | 230 | 280 | 330 | 450 | 600 | 640 | 650 |
Dimensions: (HxWxD) mm | 1400 x 555 x 740 | 1400 x 800 x 740 | |||||||
Remote signalling | Voltage-free contact | ||||||||
Remote command | EPo and bypass | ||||||||
Communication | Double RS232 + remode contacts + 2 communication interface slots | ||||||||
Operation temperature | 0 oC ~ 40 oC | ||||||||
Relative humidity | < 95% non condensing | ||||||||
Color | Light gray RAI7035 | ||||||||
Noise dBA at 1m | 54 | 60 | 62 | 63 | |||||
Protection rating | IP20 | ||||||||
Efficiency Smart mode | Up to 98% | ||||||||
Standard compliance | European Directive: I V 2006/95/CE; EMC2004/108EC; Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2 |
Parattakorn Industrial solutions Co., Ltd.
55/238 ม. 5 หมู่บ้าน ปริชาต ซ. 9 ต. บางคูวัด อ. เมือง จ. ปทุมธานี 12000
Tel : 086-5598876 / 02-9770372 / Fax : 029770372
Email : saartkla@gmail.com / www.rathakorn.com
InputGermin-XPOutput3Phase10KVAเครื่องสำรองไฟUPS120KVA